Skip to Content
Kyoritsu 5410 RCD Tester (80V - 450V)

Price:

941.00


Central Tools 3C301 – STORM™ Digital Caliper, Range: 0-6”/0-150mm
Central Tools 3C301 – STORM™ Digital Caliper, Range: 0-6”/0-150mm
65.99
65.99
Jonard TK-120 Fiber Prep Kit Basic
Jonard TK-120 Fiber Prep Kit Basic
383.95
383.95

Kyoritsu 5410 RCD Tester (80V - 450V)

https://www.etisupply.com/web/image/product.template/1058329/image_1920?unique=dc15e26

941.00 941.0 USD 941.00

Not Available For Sale

(941.00 / Units)

  • Brand

This combination does not exist.

Terms and Conditions
30-day money-back guarantee
Shipping: 2-3 Business Days

RCD TESTER

KEW 5410

Measurement of RCD trip time

 Conducting testing of rated residual non-operating currents at × 1/2 Range, measuring RCD trip time at × 1 and × 5 Ranges

  • Measurement of RCD trip time
    Conducting testing of rated residual non-operating currents at × 1/2 Range, measuring RCD trip time at × 1 and × 5 Ranges
  • Measurement of trip out current
    Measuring trip out current by varying current automatically
  • Remote Test
    Enabling a user to hold the Test Leads with his both hands by locking the Test Button
    Measurement will automatically start when the main voltage is detected
  • Voltage Measurement
    Carrying out a constant measurement of voltage in the stand-by mode at each Range
  • Auto-detection of Contact voltage
    Detecting the voltage to earth of Earth electrodes or Protective conductors during RCD test
    - when applying test currents - at measurement using EARTH in order to prevent electrical shocks caused by the damaged earth
    Measurement will be ceased at AC50V or more
  • Dust and Water proof
    Dust and Water proof construction (designed to IEC 60529 IP54)
  • Backlight
    Facilitating working at dimly illuminated locations

3D View

Specification

Measurement of RCD trip time - Measurement of trip out current


Range
× 5× 1× 1/2AUTO RAMP(mA)
Rated Voltage100V±10%
200V-10 to +32%
400V±10%
50/60Hz
Test current15/30/50/100mA15/30/50/100/200/500mA
Measuring rangeTesting time
0 to 200ms
Testing time
0 to 2000ms
40 to 110% of lΔn
(goes up by 5%)
Testing time
300ms × 15steps
AccuracyTrip Time1%rdg±3dgtTest Current at each step
-4 to +4%
Trip Time+2 to +8%dgt-8 to -2%dgtTest Current at each step
-4 to +4%

Voltage Measurement


Measuring range80 to 450V 50/60Hz
Accuracy2%rdg±4dgt
Applicable standardsIEC 61010-1 CAT Ⅲ 300V / CAT Ⅱ 400V Pollution degree2
IEC 61010-031, IEC 61557-1, 6 IEC 60529 (IP54)
Display1999 counts (3 1/2digits), Large LCD
Operating temperature
and humidity range
0 to 40ºC, relative humidity 85% (no condensation)
Storage temperature
and humidity range
-20 to 60ºC, relative humidity 75% (no condensation)
Insulation resistance50MΩ or more / 1000V (between electrical circuit and enclosure)
Sleep Function(1)Automatically enters Sleep mode in 3 minutes after the last switch operation (current consumption 75µA). This function doesn't work at voltage measurements. To exit from the Sleep mode, set the Function switch to OFF position once, and re-set it to the Range at which a measurement to be conducted. (2) Backlight turns off in 1 minute after it lights up.
Power sourceDC 12V / R6(AA)(1.5V) × 8
Dimension
167(L)×186(W)×89(D)mm
Weight
Approx. 965g (including batteries)
Possible number of Measurements
1200 times or more (measure every 30 seconds at ×1/2 Range, lΔn=100mA)
Accessories
7128A (Test leads)
7129A (Test lead with alligator clip)
8017 (Extension prod long) × 2
9121 (Shoulder strap)
9147 (Cord case)
Instruction manual, R6(AA) × 8

* Only the RCD type G (without trip out time-delay) can be tested at Auto Ramp Test, type S (time-delay) cannot be tested.

Accessories

Catalog & Document

Brand Kyoritsu