Kyoritsu 2433 Digital AC Leakage Current Clamp Meter (jaw: 40mm dia.)

Price:

$ 427.00


Kyoritsu 2432 Digital AC Leakage Current Clamp Meter (jaw: 40mm dia.)
Kyoritsu 2432 Digital AC Leakage Current Clamp Meter (jaw: 40mm dia.)
$ 540.00
$ 540.00
Kyoritsu 2433R Digital AC Leakage Clamp Meter with True RMS (jaw: 40mm dia.)
Kyoritsu 2433R Digital AC Leakage Clamp Meter with True RMS (jaw: 40mm dia.)
$ 452.00
$ 452.00

Kyoritsu 2433 Digital AC Leakage Current Clamp Meter (jaw: 40mm dia.)

https://www.etisupply.com/web/image/product.template/1058284/image_1920?unique=b43e63a

$ 427.00 427.0 USD $ 427.00

Not Available For Sale

($ 427.00 / Units)

  • Brand

This combination does not exist.

 
Terms and Conditions

Product images shown are for illustration purposes only and may not be an exact representation of the product.

LEAKAGE CLAMP METER

MODEL 2433

Frequency Selector Switch to eliminate the effect of harmonics

  • Frequency Selector Switch to eliminate the effect of harmonics
  • Three ranges: 40/400mA/400A
  • Minimum resolution 0.01mA

Specification

AC A (50/60Hz)40/400mA/400A
±1%rdg±5dgt (40/400mA)
±1%rdg±5dgt (0 to 350A)
±2%rdg (350.1 to 399.9A)
AC A (WIDE)40/400mA/400A
±2.5%rdg±10dgt [20Hz to 1kHz] (40/400mA)
±2.5%rdg±10dgt [40Hz to 1kHz] (0 to 350A)
±5%rdg [40Hz to 1kHz] (350.1 to 399.9A)
Maximum circuit voltage600V AC/DC (between line/neutral)
300V AC/DC (against earth)
Conductor sizeφ40mm max.
Frequency response20Hz to 1kHz [40Hz to 1kHz:400A]
Effect of External Stray Magnetic FieldApprox. 10mA AC in proximity to a 15mm
conductor carrying 100A AC
Safety StandardIEC 61010-1 CAT III 300V Pollution Degree 2
IEC 61010-2-032
Response TimeApprox. 2 seconds
Power sourceR03 (DC1.5V) × 2
Dimension185(L) × 81(W) × 40(D)mm
WeightApprox. 270g (including battery)
Accessories9097 (Carrying Case)
R03 (1.5V) × 2
Instruction Manual

Accessories

Catalog & Document

Brand Kyoritsu